Require a configuration-specific compatibility matrix, not a cooling label. NVIDIA’s DGX GB200 SuperPOD architecture explicitly combines liquid and air cooling. A facility assessment for that configuration must therefore address both heat-removal paths. This example should not be generalised into specifications for every AI rack. (docs.nvidia.com)
Use the following proposed procurement matrix:
| Interface | Buyer evidence requirement |
|---|---|
| Electrical supply | Approved rack power envelope, feeds, protection, connectors, distribution and required failure-mode capability |
| Liquid circuit | Manufacturer-approved coolant, supply/return conditions, flow, pressure, materials, filtration and connection interfaces |
| Heat rejection | Capacity at the relevant design conditions, shared loads and required maintenance/degraded modes |
| Residual air cooling | Non-liquid-cooled rack components, network equipment and other room loads |
| Controls | Leak detection, isolation, alarm routing, shutdown responsibility and IT/operational-technology integration |
| Physical deployment | Filled rack weight, structural review, handling route, clearances, hoses, cable paths and maintenance access |
| Commercial boundary | Who supplies, installs, cleans, fills, tests, operates and warrants each interface |
NVIDIA’s Mission Control documentation assigns different leak-detection functions across trays, racks and facility systems and identifies customer-provided building-management-system requirements. This is a concrete reason to make controls ownership part of procurement rather than leaving it to post-delivery integration. (docs.nvidia.com)
OCP’s pre-commissioning guidance addresses technology-cooling-system pipework cleaning, hydrotesting, flushing and preparation. Its stated scope does not include commissioning the CDUs and racks themselves. Request both the pipework preparation records and the additional equipment/system acceptance evidence. (opencompute.org)
Scoring rule: an unresolved interface capable of preventing the intended deployment holds G5. Strong evidence elsewhere in the cooling design cannot compensate for it.